SW Battery Charger
High efficiency QMAX battery chargers allows to charge 12v,24v or 48V batteries
Battery profiles
Generator Compatible
Alta eficiencia 95%
Carga en 4 estados
High Efficiency +95%
Vin tolerance +10%/-15%
Output Current 45A / 40A / 30A
More compacts, little space required and low weight. Max power output 1,5kW. Allows Parallel.
FEATURES
Output current settings 25,50,75,100%
Battery temperature compensation function.
Battery type selection.
Special configurations of load profiles.
Maximum energy efficiency: more than 95% that ensure a minimum loss in the conversion.
4-stage charging cycle that maximizes battery life.
Adaptable to all accumulation technologies.
Greater precision and response speed in current and voltage control.
COMPONENTS
High temperature capacitors
Modular design
Transfer contactors on load
ACCESSORIES
Communication RS 485
Status and indicators leds
Charge current ripple that minimizes battery temperature improving the charge cycle.
Input resettable thermal fuse.
Overtemperature protection
Output current limit at constant current.
Electronic input overcurrent protection.
Battery polarity inversion by internal fuse.
Protección por error de configuración de banco de baterías.
Model | QM-4830-SW | QM-2440SW | QM-1245SW |
Output Current (A) | 30 | 40 | 45 |
Output voltage (V) | 40 A 62.4 | 20 A 32 | 10 A 16 |
Stage 2 Voltage (V) | 56.4 A 57.6 | 28.2 A 28.8 | 14.1 A 14.4 |
Stage 3 Voltage (V) | 54 A 55.2 | 27 A 27.6 | 13.5 A 13.8 |
Tensión Ecualización (V) | 60 A 62.4 | 30 A 31.2 | 15 A 15.6 |
Input Voltage (VAC) | 187VAC A 242VAC | ||
Input Current (A) | 14AMP | 10AMP | 6AMP |
Performance | 95% máx. | 90% máx. power | ||
Battery Type | PB lead, PB Cal, AGM, Lithium | ||
Operating Temperature (°C) | De 10 a 45°C no condensation | ||
Battery Plug | Anderson S-B 50 | ||
Size | 19 width- 25 length- 11 height | ||
Weight | 3,5kg | ||
Warranty | 5 years | ||
Sensor Temp. Bat | Yes - Optional | ||
Protections | Input resettable thermal fuse. | ||
Overtemperature power control | |||
Output current limit at constant current. | |||
Electronic input overcurrent protection. | |||
Battery polarity inversion by internal fuse. | |||
Battery configuration error protection | |||
Modes | 2 steps | ||
4 steps |